Indoor Vacuum Circuit Breaker

VS1--Vacuum-Circuit-Breaker-handrill

VS1-12 Indoor Vacuum Circuit Breaker 12kv VCB for Medium Voltage switchgear indoor type 

 

VS1-12 indoor vacuum circuit breaker is designed for three-phase AC 50Hz power systems with rated voltage from 3.6kV to 12kV. It is mainly used for control and protection in industrial and mining enterprises, power plants, substations, and is especially suitable for frequent operation occasions.

With perfect mechanical and electrical interlocking, it can match all mainstream medium voltage switchgears. It is widely used in chemical industry, metallurgy, manufacturing, real estate, hospitals, transportation, subway and high-speed rail projects.

Product Features

  • Adopt composite insulation structure and integrated spring operating mechanism.
  • Stable electrical and mechanical performance, long service life.
  • Can be used as fixed type or equipped with cart to become handcart type.
  • Strong compatibility, matches all mainstream 12kV switchgears.
  • Compact structure, small size, light weight, easy for installation and maintenance.
  • Perfect interlock device ensures safe operation and prevents misoperation.

Technical Parameters

No. Item Unit Value
1 Rated Voltage kV 12
2 Rated Frequency Hz 50/60
3 1min Power Frequency Withstand Voltage kV 42
4 Lightning Impulse Withstand Voltage kV 75
5 Rated Current A 630, 1250, 1600, 2000, 2500, 3150
6 Rated Short-circuit Breaking Current kA 20, 25, 31.5, 40
7 Rated Short-time Withstand Current (4s) kA 20, 25, 31.5, 40
8 Rated Peak Withstand Current kA 50, 63, 80, 100
9 Opening Time ms 20–50
10 Closing Time ms 35–70
11 Mechanical Life times 10000
12 Control Voltage V AC110/220, DC110/220
1.Ambient Temperature: No more than + 40℃ and no less than – 15℃.Average temperature is no more than +35℃ within 24 hours. 2.Altitude: No more than 1000m. 3.Relative Humidity: the average daily value is no more than 95%, the average monthly value is no more than 90%. 4.Earthquake Intensity: No more than 8 degrees. 5.Vapor pressure: average daily value is no more than 2.2kPa, average monthly value is no more than 1.8kPa. 6.Installation locations without fire, explosion danger, serious pollution, chemical corrosion and violent vibration.

Normal Operating Conditions

  • Ambient Temperature: -15℃ ~ +40℃, average ≤35℃ in 24h
  • Altitude: ≤ 1000m
  • Relative Humidity: daily average ≤95%, monthly average ≤90%
  • Earthquake Intensity: ≤ 8 degrees
  • Installation site: no fire, explosion, corrosion, dust or vibration

Application

VS1-12 vacuum circuit breaker is widely used in power plants, industrial and mining enterprises, petrochemical, metallurgy, infrastructure, residential districts, hospitals, transportation, subway, high-speed rail and other medium voltage power distribution systems.