Oil-Immersed Transformer

S11-M oil-immersed power-transformer

S22-M Oil-Immersed Power Transformer


S20-M series sealed oil-immersed transformers are high-efficiency, energy-saving power distribution equipment with fully sealed structure, low loss, low noise, and maintenance-free design. They are widely used in urban and rural power grids, industrial and mining enterprises, commercial buildings, and various power distribution systems.
Adopting high-quality silicon steel sheets and advanced technique, the no-load loss is greatly reduced. The fully sealed structure isolates the transformer oil from air, preventing moisture and oxidation, effectively extending service life and ensuring stable and safe operation for a long time.
This series complies with GB/T 6451, GB/T 1094, IEC 60076 and other international and domestic standards, with strong short-circuit resistance, low temperature rise, and reliable performance.

Model: S22-M-□/□
SymbolMeaning
SThree-phase
22Performance design serial number
MFully sealed structure
First □Rated capacity (kVA)
Second □Voltage class (kV)

Product Features


1. High Efficiency & Low Loss
Optimized core and coil design, lower no-load loss and load loss, obvious energy-saving effect.
2. Fully Sealed & Maintenance-Free
Corrugated tank or sealed structure, no oil replacement, no maintenance required during service life.
3. Strong Short-Circuit Withstand Ability
Reinforced winding structure, excellent mechanical strength, can withstand short-circuit impact.
4. Low Noise & Stable Operation
Low noise design, reliable insulation, long service life, suitable for outdoor long-term operation.
5. Wide Application Range
Suitable for 10kV, 35kV power distribution systems, urban grid, industrial and mining, infrastructure and other fields.

Operating Condition

Item Specification
Altitude ≤ 1000m
Ambient temperature -25℃ ~ +40℃
Installation Outdoor / indoor
Frequency 50Hz / 60Hz

Technical Parameters

S22-M 10kV Series Oil-Immersed Transformer Full Technical Parameters
ModelHigh Voltage(kV)Tap RangeLow Voltage(kV)Vector GroupNo-load Loss(W)Load Loss(Dyn11/Yzn11, W)Load Loss(Yyn0, W)No-load Current(%)Impedance(%)
S22-M-3010±2×2.5% / ±5%0.4Dyn11 / Yyn0654554301.54.0
S22-M-5010±2×2.5% / ±5%0.4Dyn11 / Yyn0806556251.34.0
S22-M-6310±2×2.5% / ±5%0.4Dyn11 / Yyn0907857451.24.0
S22-M-8010±2×2.5% / ±5%0.4Dyn11 / Yyn01059459001.24.0
S22-M-10010±2×2.5% / ±5%0.4Dyn11 / Yyn0120114010801.14.0
S22-M-12510±2×2.5% / ±5%0.4Dyn11 / Yyn0135136012951.14.0
S22-M-16010±2×2.5% / ±5%0.4Dyn11 / Yyn0160166515851.04.0
S22-M-20010±2×2.5% / ±5%0.4Dyn11 / Yyn0190197018701.04.0
S22-M-25010±2×2.5% / ±5%0.4Dyn11 / Yyn0230230021950.94.0
S22-M-31510±2×2.5% / ±5%0.4Dyn11 / Yyn0270276026300.94.0
S22-M-40010±2×2.5% / ±5%0.4Dyn11 / Yyn0330325030950.84.0
S22-M-50010±2×2.5% / ±5%0.4Dyn11 / Yyn0385390037100.84.0
S22-M-63010±2×2.5% / ±5%0.4Dyn11 / Yyn046044600.64.5
S22-M-80010±2×2.5% / ±5%0.4Dyn11 / Yyn056054000.64.5
S22-M-100010±2×2.5% / ±5%0.4Dyn11 / Yyn066574150.64.5
S22-M-125010±2×2.5% / ±5%0.4Dyn11 / Yyn078086400.54.5
S22-M-160010±2×2.5% / ±5%0.4Dyn11 / Yyn0940104400.54.5
S22-M-200010±2×2.5% / ±5%0.4Dyn11 / Yyn01085131800.45.0
S22-M-250010±2×2.5% / ±5%0.4Dyn11 / Yyn01280133600.45.0

Outline dimension & Install Dimension

S13-M oil-immersed power transformer appearance and installation dimensions

We'd like to work with you!

Send us a message if you have any questions or request a quote.Our experts will give you a reply within 24 hours and help youselect the right valve you want.
Anything we should know