DW1-3200 belongs to DW1 series mainstream low-voltage ACB, designed for 50Hz, 380V/660V power distribution systems, serving as core main switch for Factory substation, industrial production line, large data center auxiliary power. It integrates complete circuit protection, dual installation modes, and stable operation performance, fully compliant with GB/T 14048.1/2 & IEC 60947-1/2 standards.
| Series Model | Frame Current (In) | Rated Working Voltage | Typical Application Scenarios |
|---|---|---|---|
| DW1-1000 | 1000A | AC 380V/660V 50Hz | Medium power distribution, factory workshop main switch, commercial building power supply |
| DW1-1600 | 1600A | Large workshop distribution, high-rise building distribution room, industrial equipment main power | |
| DW1-2000 | 2000A | Industrial park distribution, large shopping mall, hospital main power system | |
| DW1-3200 | 3200A | Factory substation, industrial production line, large data center auxiliary power | |
| DW1-4000 | 4000A | Medium-sized substation, heavy industry workshop, commercial complex main switch | |
| DW1-6300 | 6300A | Large substation, heavy industry production base, municipal power distribution network | |
| DW2-1000 | 1000A | AC 380V/660V 50Hz | Upgraded medium distribution, frequency conversion equipment power, marine auxiliary power |
Note: All DW1/DW2 series ACB are designed for low-voltage power distribution systems, providing overcurrent, short-circuit and under-voltage protection for power supply lines and electrical equipment.
The DW1-3200 universal air circuit breaker is a heavy‑duty low‑voltage electrical device for AC 50Hz power distribution systems, with rated working voltage AC 380V/660V and rated frame current 3200A. Complying with GB/T 14048.2 and IEC 60947-2 standards, it adopts an optimized structure and high‑performance contact system, suitable for large‑capacity power distribution and short‑circuit protection in industrial and infrastructure fields.
It is equipped with advanced thermal‑magnetic or electronic tripping units, realizing full protection against overload, short circuit, undervoltage, phase loss and other faults. With high breaking capacity, low temperature rise and long mechanical life, it is widely used in factory substations, large industrial production lines, data centers, energy projects and other high‑power applications.
| Parameter Category | Parameter Item | DW1-3200 Specification |
|---|---|---|
| Basic Electrical Parameters | Rated Working Voltage (Ue) | AC 380V / AC 660V |
| Rated Frame Current (In) | 3200A | |
| Rated Frequency (f) | 50Hz | |
| Short-Circuit Breaking Capacity | Rated Ultimate Breaking Capacity (Icu) @ 380V | 70kA |
| Rated Service Breaking Capacity (Ics) @ 380V | 50kA | |
| Peak Withstand Current (Icw) @ 380V | 140kA | |
| Rated Breaking Capacity @ 660V | 45kA | |
| Tripping Characteristics | Tripping Type | Thermal-magnetic / Electronic (optional) |
| Instant Tripping Current | 10~14In (short circuit) | |
| Overload Tripping Time | Inverse time characteristic (1.05In no trip for 2h; 1.3In trip within 2h) | |
| Mechanical Performance | Mechanical Life | 10,000 times |
| Electrical Life | 5,000 times | |
| Structural Parameters | Pole Number | 3P / 4P |
| Protection Grade | IP30 | |
| Installation Method | Fixed type / Draw-out type | |
| Environmental Parameters | Working Temperature | -5℃ ~ +40℃ (≤95% humidity, no condensation) |
| Pollution Degree | 2 | |
| Compliance Standards | National & International Standards | GB/T 14048.2, IEC 60947-2 |