RCBO RCCB with Overcurrent Protection

DZ47LE-125H RCBO RCCB with Overcurrent Protection

DZ47LE-125H 4.5kA RCBO RCCB with Overcurrent Protection

Overview:
DZ47LE-125H type rcbo mainly used for AC 50Hz or 60Hz, rated voltage 230V~240V for 1 pole and 2 poles, 400V~415V for 3 poles and 4 poles, rated working current from 63A to 125A and immediately cut off power supply once someone suffers from electric shock or leakage current above specified value. It can effectively protect personal security and avoid damage to equipment. The circuit-breaker can also function as overload and short-circuit protection and unfrequented changeover of line under normal condition. 

Parameters

Standard IEC/EN61009-1 IEC/EN60947-2
Protection Ground fault, Overcurrent and short circuit, Over-voltage(selectable)
Type of trip Ground fault: Electronic
Overload and short circuit: Thermo-magnetic
Type of protection(electric leakage) AC, A, S
No. of poles 1P+N 3module, 2P 4.5module, 3P/3P+N 6module, 4P 7.5module, N line with disconnected
Rated currents(In) 63, 80, 100, 125A
Rated sensitivity currents(I△n) 30, 100, 300mA
Residual current off-time under (I△n) ≤0.1s
Rated residual making and breaking capacity(I△m) 500A (In≤50A), 10In (In>50A)
Rated voltage(Ue) 1P+N, 2P: 230/240V~ ; 3P ; 3P+N: 4P ; 400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 4,500A
Rated impulse withstand voltage(1.2/50)Uimp 4,000V
Dielectric test voltage at Ind.Freq.for 1 min 2kV
Thermal release characteristic (1.13-1.45)xIn (1.05-1.30)xIn
Magnetic release characteristic B:(3-5)xIn, C:(5-10)xIn, D(10-20)xIn (8-12)xIn
Electrical life 4,000Cycles
Mechanical life 10,000Cycles
Contact position indicator Yes
Ground fault indicator Yes
Protection degree IP20
Ambient temperature -25℃ to +40℃, Max. 95% humidity
Terminal connection type Cable/Pin-type busbar
Max. terminal size for cable 50mm²
Max. tightening torque 3.5N.m
Installation Mounting on 35mm DIN rail
Connection From Top and bottom

Diagram

DZ47-63 diagram

Install Dimension

DZ47LE-125H install dimension