Dry Type Transformer

SC(B)H15 amorphous alloy epoxy dry-type transformer

SC(B)15 Amorphous Alloy Epoxy Dry Type Power Transformer

The amorphous alloy epoxy dry-type transformer by applying advanced HTT epoxy dry-type transformer manufacturing technology. This product features low partial discharge, low loss, excellent heat dissipation, strong moisture resistance, outstanding short-circuit resistance, high overload capacity and compact appearance. Its performance fully complies with the standard GB/T 22072 Technical Parameters and Requirements for Amorphous Alloy Iron Core Distribution Transformers. Compared with Group A transformers specified in GB/T 10228, its no-load loss is reduced by more than 70%, and load loss is reduced by 15%, making it a new generation of energy-saving, safe, green and environmentally friendly high-tech electrical product. This transformer can replace all ordinary dry-type transformers in their application scenarios, suitable for high-rise buildings, commercial centers, subways, airports, stations, mining enterprises and power plants. It is especially ideal for places with high fire safety requirements (flammable and explosive environments) and high moisture resistance demands.

Model Naming Rule: S C □ H 15 – □ / □

SymbolMeaning
SThree-phase
CCast solid insulation
HAmorphous alloy iron core
15Performance level code
□ (before /)Rated capacity (kVA)
□ (after /)Voltage class (kV)
Additional Mark (Optional)B: Enameled wire; L: Aluminum conductor

Reference Standard

GB/T1094.11; GB/T1028; IEC60076; DIN42523.1; GB/T22072

Note: The actual installation dimensions are subject to the overall outline drawing provided when ordering. Noise-absorbing shells can be configured according to customer needs, reducing noise by more than 10dB compared with ordinary shells.

Product Features

□ Rated capacity: 30-2000 kVA
□ Voltage class: 0.4-10 kV
□ Phase number: Three-phase or single-phase
□ Frequency: 50Hz or 60Hz
□ Insulation class: Class F, average temperature rise of winding ≤ 100K
□ Cooling method: AN or AF
□ Protection class: IP00, IP20 or IP23
□ Performance parameters: See parameter table above

1. Iron Core Structure
The iron core is made of formed amorphous alloy material with a three-phase three-column structure. It is suspended on the reinforced insulating plate above the coil, completely free from external force, giving full play to the advantages of amorphous alloy material: low no-load loss and low no-load current.

2. Coil & Insulation Performance
Both high and low voltage windings adopt rectangular coils, filled and wound with imported glass fiber mesh and tape inside and outside, and cured integrally with resin penetration. This structure provides extremely strong crack resistance and short-circuit resistance. The fully cast coil has strong moisture resistance and can be powered on immediately after installation.

3. Overall Structure
The transformer adopts a pusher-type clamp structure, with coils tightened by elastic pressure nails, resulting in a simple and beautiful overall structure. The high and low voltage windings are of thin-insulation, low-filler, fully cast type, with extremely strong moisture resistance, making it an immediate power-on transformer.

4. Casting Process & Quality Control
The product is cast with the latest German HEDRICH vacuum casting equipment, featuring advanced technologies such as vacuum thin film degassing, metering pump and static mixing, ensuring the proportioning accuracy and casting quality of epoxy mixture. The partial discharge of the winding is less than 5PC.

5. Heat Dissipation & Mechanical Strength
The HTC winding adopts advanced “air duct bar” technology, which is not limited by the winding curvature radius. Axial air ducts can be set at the heating center of the winding according to design requirements, achieving optimal heat dissipation for the whole machine. Multiple support ribs can be generated in the air duct to effectively enhance the mechanical strength of the winding.

Operating Condition

Condition ItemSpecification
Altitude≤ 1000m
Application EnvironmentIndoor use
Ambient TemperatureMax: 40℃; Min: -30℃; Daily average: 30℃
Relative Humidity95% (25℃, daily average); 90% (25℃, monthly average)

Insulation Level

Voltage Class (kV)Max Equipment Voltage (kV, rms)Rated Short-time Power-frequency Withstand Voltage (kV, rms)Rated Lightning Impulse Withstand Voltage (kV, peak)
≤1≤1.1320
33.61040
67.22060
10123575

Note: High voltage (kV): 11, 10.5, 10, 6.6, 6.3; Low voltage (kV): 0.4; Connection group: Dyn11; Insulation level: LI75AC35/L 10AC3

Technical Parameters

Unit: mm; Weight unit: kg

Rated Capacity (kVA)P0 (W)Pk (120℃) (kVA)I0 (%)Uk (%)Overall DimensionsInstallation DimensionsMain Unit Weight (kg)
Length (L)Width (B)Height (H)Horizontal × Vertical (a×b)
30707101.64920600750450550 600
50 90 1000 1.4 940 600 800 450550730
8012013801.31000600870450550 900
100 130 1570 1.2 1000 600 890 4505501030
12515018501.11060600920450550 1100
160 170 2130 1.1 1100 710 940 4506601300
2002002530111407101000450660 1420
250 230 2760 1 1200 710 1050 4506601580
31528034700.912609001080550820 1800
400 310 3990 0.8 1320 900 1095 6608202340
50036048800.8613809001200660820 2600
630 410 5880 0.7 1460 900 1230 6608202840
80055059600.715609001250820820 3350
1000 550 6960 0.6 1600 900 1300 8208204020
125065081300.617609001440820820 4250
1600 760 9690 0.6 1860 900 1530 8208205500
20001000117300.518609001750820820 6530
2500 1200 14450 0.5 2040 900 1930 8208207540

Outline dimension & Install Dimension