| Standard |
IEC/EN61009-1 |
| Protection |
Ground fault, Overcurrent and short circuit, Over-voltage(selectable) |
| Type of trip |
Ground fault: Electronic Overload and short circuit: Thermo-magnetic |
| Type of protection (electric leakage) |
AC, A, S |
| No. of poles |
1P+N 3module, 3P+N 5module, N line with disconnected |
| Rated currents (In) |
6,10,16,20,25,32,40,50,63A |
| Rated sensitivity currents I△n |
10,30,100,300mA |
| Residual current off-time under I△n |
≤0.1s |
| Rated residual making and breaking capacity(I△m) |
500A (In≤50A), 10In (In>50A) |
| Rated voltage (Ue) |
1P+N:230/240V~,3P+N:400/415V~ |
| Rated frequency |
50/60Hz |
| Rated breaking capacity |
4,500A |
| Rated impulse with standard voltage (1.5/50) Uimp |
4,000V |
| Dielectric test voltage at Ind. Freq. for 1min |
2kV |
| Thermal release characteristic |
(1.13-1.45) x In |
| Magnetic release characteristic |
B:(3-5) x In, C:(5-10) x In, D:(10-20) x In |
| Electrical life |
4,000Cycles |
| Mechanical life |
10,000Cycles |
| Contact position indicator |
Yes |
| Ground fault indicator |
Yes |
| Protection degree |
IP20 |
| Ambient temperature |
-25℃ to +40℃, Max.95% humidity |
| Terminal connection type |
Cable/Pin-type busbar |
| Max. terminal size for cable |
25mm2 |
| Max. tightening torque |
2.5N.m |
| Installation |
Mounting on 35mm DIN rail |
| Connection |
From top |