Products

DZ47LE-63A residual Current operated Circuit Breaker  with Overcurrent protection rcbo

DZ47LE-63 4.5kA RCBO RCCB with Overcurrent Protection

Overview:
DZ47LE-63  type rcbo mainly used for AC 50Hz or 60Hz, rated voltage 230 or below and rated working current 63A or below and immediately cut off power supply once someone suffers from electric shock or leakage current above specified value. It can effectively protect personal security and avoid damage to equipment. The circuit-breaker can also function as overload and short-circuit protection and unfrequented changeover of line under normal condition. A Residual Current Operated Circuit Breaker (RCBO) is a critical safety measure when protecting electrical circuits, helps in protecting people and terminal equipment from electrical accidents.

Parameters

Standard IEC/EN61009-1
Protection Ground fault, Overcurrent and short circuit, Over-voltage(selectable)
Type of trip Ground fault: Electronic
Overload and short circuit: Thermo-magnetic
Type of protection (electric leakage) AC, A, S
No. of poles 1P+N 3module, 3P+N 5module, N line with disconnected
Rated currents (In) 6,10,16,20,25,32,40,50,63A
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A (In≤50A), 10In (In>50A)
Rated voltage (Ue) 1P+N:230/240V~,3P+N:400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 4,500A
Rated impulse with standard voltage (1.5/50) Uimp 4,000V
Dielectric test voltage at Ind. Freq. for 1min 2kV
Thermal release characteristic (1.13-1.45) x In
Magnetic release characteristic B:(3-5) x In, C:(5-10) x In, D:(10-20) x In
Electrical life 4,000Cycles
Mechanical life 10,000Cycles
Contact position indicator Yes
Ground fault indicator Yes
Protection degree IP20
Ambient temperature -25℃ to +40℃, Max.95% humidity
Terminal connection type Cable/Pin-type busbar
Max. terminal size for cable 25mm2
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top

Diagram

DZ47-63 diagram

Install Dimension

DZ47LE-63 install dimension

We'd like to work with you!