DZ20Y series molded case circuit breakers (MCCB) are industrial-grade protection devices designed for AC 50Hz power distribution systems with rated operational voltage up to 380V (Ui=660V) and rated current ranging from 100A to 1250A. They provide reliable protection against overload, short-circuit, and under-voltage for distribution lines and power equipment, and can also be used for infrequent circuit switching and motor starting under normal operating conditions.
Compared with DZ15 series (small current, economical type for civil use), DZ20Y features higher short-circuit breaking capacity (Icu=30~40kA), wider current range, support for 3P/4P pole configuration, and compatibility with various accessories (auxiliary contacts, alarm contacts, undervoltage release, etc.). The series complies with GB/T 14048.2, JB/T 8589 and IEC 60947-2 standards, with optional white cover or transparent cover versions to meet different application requirements.
• Wide rated current range: 100A ~ 1250A (divided into 100/225/400/630/1250 frame sizes)
• High short-circuit breaking capacity: Icu=30~40kA, suitable for industrial high-current scenarios
• Support 3P/4P pole configuration, compatible with three-phase four-wire power supply system
• Optional transparent cover (visual internal structure) or white cover (better dustproof performance)
• Complete accessory compatibility: auxiliary contact, alarm contact, undervoltage release, electric operating mechanism
• Long mechanical/electrical life: mechanical life up to 10,000 times, electrical life up to 2,000 times
• Wide operating temperature range: -5℃ ~ +40℃, suitable for various industrial environments
Example: DZ20Y-400/3310
• DZ: Molded case circuit breaker
• 20: Design serial number
• Y: General type (standard breaking capacity)
• 400: Frame rated current (400A)
• 3: 3 poles
• 3: Thermal-magnetic release
• 1: With undervoltage release
• 0: Without auxiliary contact
Common suffix combinations:
• 3300: 3 poles + thermal-magnetic release + no accessories
• 3310: 3 poles + thermal-magnetic release + undervoltage release
• 4300: 4 poles + thermal-magnetic release + no accessories
| Parameter Category | Parameter Item | DZ20Y-100 | DZ20Y-225 | DZ20Y-400 | DZ20Y-630 | DZ20Y-1250 | Unit |
|---|---|---|---|---|---|---|---|
| Basic Electrical Parameters | Rated Operational Voltage (Ue) | 380 | 380 | 380 | 380 | 380 | V |
| Rated Insulation Voltage (Ui) | 660 | 660 | 660 | 660 | 660 | V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 | 6 | 6 | 6 | 6 | kV | |
| Rated Frequency (f) | 50 | 50 | 50 | 50 | 50 | Hz | |
| Rated Current (In) | 16~100 | 100~225 | 250~400 | 400~630 | 630~1250 | A | |
| Pole Number | 3P/4P | 3P/4P | 3P/4P | 3P/4P | 3P/4P | – | |
| Short-circuit Breaking Capacity | Rated Ultimate Short-circuit Breaking Capacity (Icu) | 30 | 30 | 35 | 35 | 40 | kA |
| Rated Service Short-circuit Breaking Capacity (Ics) | 15 | 15 | 17.5 | 17.5 | 20 | kA | |
| Peak Short-circuit Withstand Current (Icw) | 63 | 63 | 80 | 80 | 100 | kA | |
| Tripping Characteristics | Overload Tripping (1.05In) | No trip in 2h | No trip in 2h | No trip in 2h | No trip in 2h | No trip in 2h | – |
| Overload Tripping (1.30In) | Trip in <2h | Trip in <2h | Trip in <2h | Trip in <2h | Trip in <2h | – | |
| Short-circuit Instantaneous Tripping (10In) | Trip <0.2s | Trip <0.2s | Trip <0.2s | Trip <0.2s | Trip <0.2s | – | |
| Undervoltage Tripping Voltage Range | 70%~35% Ue | 70%~35% Ue | 70%~35% Ue | 70%~35% Ue | 70%~35% Ue | – | |
| Mechanical Characteristics | Mechanical Life | 10000 | 10000 | 8000 | 8000 | 6000 | Times |
| Electrical Life | 2000 | 2000 | 1500 | 1500 | 1000 | Times | |
| Operating Temperature Range | -5℃ ~ +40℃ | ℃ | |||||
| Protection Grade | IP Rating (Case) | IP30 | – | ||||
| Standards Compliance | Applicable Standards | GB/T 14048.2, JB/T 8589, IEC 60947-2 | – | ||||
• DZ20Y series supports front connection and rear connection two installation methods, please select according to the actual cabinet design.
• For models with rated current ≥400A, copper bar connection is recommended to ensure good electrical conductivity and heat dissipation.
• The installation hole size must match the Φd parameter in the dimension table to avoid installation instability.
• Ensure the ambient temperature is within -5℃ ~ +40℃ during installation, and avoid direct sunlight or high humidity environments.
• After installation, check the flexibility of the operating handle and the reliability of the wiring before power-on.
Frame Size Selection:
1. DZ20Y-100: Suitable for industrial auxiliary circuits with rated current ≤100A (e.g., lighting, small power distribution)
2. DZ20Y-225: Suitable for motor protection or distribution circuits with rated current 100~225A
3. DZ20Y-400/630: Suitable for main incoming/outgoing lines of distribution cabinets with rated current 250~630A
4. DZ20Y-1250: Suitable for total incoming lines of high-power distribution cabinets with rated current 630~1250A
Accessory Selection:
• Undervoltage release (suffix 3310): Required for circuits that need undervoltage protection
• Auxiliary contact: Required for remote monitoring of breaker status
• Electric operating mechanism: Required for remote control of breaker switching
Note: The following dimensions are for front connection type. For rear connection dimensions, please contact our technical support.
Figure 1: Outline & Installation Dimensions (Front Connection)
| Model | W | L | H | W1 | L1 | L2 | H1 | H2 | H3 | A | B | Φd | Unit |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| DZ20Y-100 | 105 | 165 | 86 | 70 | — | 215 | 103 | 26 | 26 | 35 | 126 | 5 | mm |
| DZ20Y-225 | 108 | 256 | 105 | 70 | 326 | 402 | 142 | 20 | 20 | 35 | 196.5 | 4.5 | mm |
| DZ20Y-400 | 155 | 276 | 116 | 102 | 391 | — | 150 | 27 | 27 | 51 | 240 | 7 | mm |
| DZ20Y-630 | 210 | 268 | 108 | 140 | 367 | — | 147 | 22 | 22 | 70 | 200 | 7 | mm |
| DZ20Y-1250 | 212 | 393 | 142 | 140 | 559 | — | 216 | 31 | 31 | 70 | 360 | 10 | mm |