Molded Case Circuit Breaker - MCCB

DZ15 Molded Case Circuit Breake MCCB

DZ15 MCCB Molded-Case-Circuit-Breaker 40A-100A

DZ15 series molded case circuit breakers are suitable for circuits with AC 50Hz, rated operating voltage up to 380V and rated current up to 100A, for the connection, disconnection and power distribution of lines. The circuit breakers are equipped with overload and short-circuit protection devices, which can protect lines and electrical equipment against overload and short-circuit. Under normal operating conditions, the circuit breakers can also be used for infrequent switching of lines and infrequent starting of motors. This series of circuit breakers complies with the requirements of GB/T 14048.2 standard.

Main Technical Parameters

1. Basic Parameters of Circuit Breaker (see Table 1)

Table 1
Model Frame Grade Rated Current Inm(A) Pole Number Rated Insulation Voltage Ui(V) Rated Working Voltage Ue(V) Rated Current In(A) Rated Short-circuit Breaking Capacity Icu=Isc (kA) cosφ Arc Distance (mm)
DZ15-40 40 2 380 220/380 6, 10, 16, 20, 25, 32, 40 3 0.9 ≤50
DZ15-40 40 3 380 380 6, 10, 16, 20, 25, 32, 40 3 0.9 ≤50
DZ15-100 100 3 380 380 10, 20, 25, 32, 63, 80, 100 5 0.7 ≤70

2. The protection characteristics of the overcurrent release are shown in Table 2 and Table 3, and the setting accuracy of its short-circuit instantaneous protection characteristics is ±20%.

Cross-sectional Area of Connecting Wires (see Table 5)

Table 5
Rated Current (A) 6, 10 16, 20 25 32 40, 50 63 80 100
Wire Cross-sectional Area (mm²) 1.5 2.5 4 6 10 16 25 35

4. After the circuit breaker is installed, it shall be inspected in accordance with the installation requirements to ensure that its fixed connection parts are firm and reliable. Operate the circuit breaker repeatedly for several times to confirm that the operating mechanism is flexible and reliable before putting it into use.

5. The protection characteristics of the circuit breaker have been adjusted by the manufacturer at the factory. Users shall not adjust them arbitrarily during use to avoid affecting the protection performance.

6. If the circuit breaker trips due to faults (overload or short-circuit) in the control circuit, the operating handle will be in the tripped position. After identifying the cause and eliminating the fault, the circuit breaker can be reset and put into operation again.

7. After the circuit breaker interrupts a short-circuit, the cover must be opened to inspect the contacts. If the contacts are severely burnt or pitted, maintenance or replacement shall be carried out.

8. During use, storage or transportation, the circuit breaker shall not be exposed to rain, snow, or subjected to dropping impacts.

Working Condition

Normal Operating Conditions

1. Ambient air temperature:

a. The upper limit of ambient air temperature is +40℃;

b. The 24-hour average ambient air temperature shall not exceed +35℃;

c. The lower limit of ambient air temperature is -5℃.

Note: For operating conditions where the upper limit of ambient air temperature exceeds +40℃ or the lower limit is lower than -5℃, the user must consult with our factory when placing an order.

2. Altitude: The altitude of the installation site shall not exceed 2000m.

3. Atmospheric conditions: At the maximum temperature of +40℃, the relative humidity of the atmosphere shall not exceed 50%. Higher relative humidity is allowed at lower temperatures, e.g., 90% at 20℃. Special measures shall be taken for condensation occasionally formed on the product due to temperature changes.

4. Pollution degree: The pollution degree of the installation site is class 3.

5. Installation category: The installation category of the circuit breaker is class II.

6. Installation conditions: The circuit breaker shall be installed individually or in a power distribution cabinet in accordance with the instruction manual provided by our factory. The installation position shall be vertical, and the inclination angle with the vertical plane shall not exceed 5°.

7. Installation environment conditions:

a. Install in a place free from significant shaking, impact and vibration;

b. Install in a place free from rain and snow;

c. The installation site shall be free from explosive hazardous media, and there shall be no gases and dust in the medium that are sufficient to corrode metals and damage insulation.

Install Dimension

DZ15 install dimension

Table 6

Model Pole Number Outline Dimensions Installation Dimensions
A B C D a b Φd
DZ15-40 2 53 134 88 73.5 / 120 2-Φ5
3 78 134 88 73.5 25 120 4-Φ5
DZ15-100 3 96 147 96 80 30 130 4-Φ7

Important when you order

Ordering Information

Users shall specify the following contents when placing an order:

1. Name and model of the circuit breaker;

2. Rated current of the release;

3. Number of poles;

4. Application purpose;

5. Order quantity.

Example: Order 100 pieces of DZ15-40/3901 molded case circuit breakers, with 32A rated release current, 3 poles, for power distribution use.

More useful information

Protection Characteristics of Overcurrent Release for Circuit Breakers Used in Distribution Protection (see Table 2)

Table 2
Ambient Air Temperature Test Current Test Time Expected Result Initial State
+30±2℃ 1.05In ≥1h No Tripping Cold State
1.3In <1h Tripping Hot State
At Any Suitable Temperature 3.0In ≥2s Recoverable Cold State
10.0In <0.2s Tripping Cold State
+20±2℃ 1.05In ≥1h No Tripping Cold State
1.3In <1h Tripping Hot State

Note: The circuit breaker shall be recoverable when energized with 3In current for the specified time, then the test current is reduced to 90% of the rated current, and the circuit breaker shall not trip.

Protection Characteristics of Overcurrent Release for Circuit Breakers Used in Motor Protection

Table 3
Ambient Air Temperature Test Current Test Time Expected Result Initial State
+30±2℃ 1.05In ≥2h No Tripping Cold State
1.2In <2h Tripping Hot State
1.5In <2min Tripping Hot State
7.2In 2s<t≤10s Recoverable Cold State
At Any Suitable Temperature 12.0In <0.2s Tripping Cold State
-5±2℃ 1.05In ≥2h No Tripping Cold State
1.3In <2h Tripping Hot State
+40±2℃ 1.0In ≥2h No Tripping Cold State
1.2In <2h Tripping Hot State

3. Mechanical and Electrical Life of Circuit Breaker

Under specified conditions, the mechanical and electrical life of the circuit breaker is expressed by the number of operating cycles (see Table 4).

Table 4
Type of Residual Current Circuit Breaker Rated Operating Conditions Operating Cycles per Hour Number of Operating Cycles
Closing Breaking cosφ With Load Without Load Total
For Distribution Protection Un In Un In 0.8 120 1500 8500 10000
For Motor Protection Un 6In 0.17Un In 0.35 120 1500 8500 10000

Note: During each operating cycle, the maximum closing time of the circuit breaker shall be 2s. When the circuit breaker for motor protection is closed with 6In current, the minimum closing time shall be 0.1s.

4. Power Frequency Withstand Voltage

The circuit breaker can withstand the power frequency withstand voltage test of AC 50Hz, 1890V for 5s without flashover and breakdown.

5. Impulse Withstand Voltage: 6kV

Structural Features

1. The circuit breaker is mainly composed of an operating mechanism, overcurrent release, contact series, arc extinguishing cover, base and cover, and all components are assembled in a plastic shell.

2. The base and cover of the circuit breaker are pressed with thermosetting insulating plastic, which has good insulation performance. The operating mechanism has the functions of quick closing and quick opening of contacts. Its “close”, “open”, “re-engage” and free tripping positions are distinguished by the handle position, and the circuit breaker is marked with “close” and “open” indicators.

3. The circuit breaker has overload and short-circuit protection functions. Its overcurrent release adopts a silicon oil resistance hydraulic release, which can provide an ideal inverse time-delay overcurrent protection characteristic.

4. The circuit breaker is available in single-pole, two-pole, three-pole and four-pole forms to meet the requirements of users for selecting different phase lines. The full series of circuit breakers are installed with screws, which is firm and reliable.

Installation, Use and Maintenance

1. Before installation, check whether the technical parameters on the nameplate are consistent with the actual requirements.

2. The circuit breaker shall be installed in accordance with specified requirements: the incoming terminal at the upper part of the circuit breaker is the power side, the outgoing terminal at the lower part is the load side, and the upward position of the handle is the contact closing position.

3. When wiring the circuit breaker, the cross-sectional area of the selected connecting wire must be suitable for the rated current. For PVC insulated copper wires, refer to Table 5 for the cross-sectional area.