DW1-4000 belongs to DW1 series mainstream low-voltage ACB, designed for 50Hz, 380V/660V power distribution systems, serving as core main switch for Medium-sized substation, heavy industry workshop, commercial complex main switch. It integrates complete circuit protection, dual installation modes, and stable operation performance, fully compliant with GB/T 14048.1/2 & IEC 60947-1/2 standards.
| Series Model | Frame Current (In) | Rated Working Voltage | Typical Application Scenarios |
|---|---|---|---|
| DW1-1000 | 1000A | AC 380V/660V 50Hz | Medium power distribution, factory workshop main switch, commercial building power supply |
| DW1-1600 | 1600A | Large workshop distribution, high-rise building distribution room, industrial equipment main power | |
| DW1-2000 | 2000A | Industrial park distribution, large shopping mall, hospital main power system | |
| DW1-3200 | 3200A | Factory substation, industrial production line, large data center auxiliary power | |
| DW1-4000 | 4000A | Medium-sized substation, heavy industry workshop, commercial complex main switch | |
| DW1-6300 | 6300A | Large substation, heavy industry production base, municipal power distribution network | |
| DW2-1000 | 1000A | AC 380V/660V 50Hz | Upgraded medium distribution, frequency conversion equipment power, marine auxiliary power |
Note: All DW1/DW2 series ACB are designed for low-voltage power distribution systems, providing overcurrent, short-circuit and under-voltage protection for power supply lines and electrical equipment.
The DW1-4000 universal air circuit breaker is an extra-high capacity low-voltage electrical device for AC 50Hz power distribution systems, with rated working voltage AC 380V/660V and rated frame current 4000A. Complying with GB/T 14048.2 and IEC 60947-2 standards, it adopts a reinforced structure and high-performance contact system, specially designed for large-capacity power distribution and short-circuit protection in heavy industry and power stations.
Equipped with high-precision electronic or thermal-magnetic tripping units, it provides complete protection against overload, short circuit, undervoltage, phase loss and other faults. With ultra-high breaking capacity, low temperature rise and long service life, it is widely used in medium-sized substations, heavy industry workshops, large commercial complexes and other high-power applications.
| Parameter Category | Parameter Item | DW1-4000 Specification |
|---|---|---|
| Basic Electrical Parameters | Rated Working Voltage (Ue) | AC 380V / AC 660V |
| Rated Frame Current (In) | 4000A | |
| Rated Frequency (f) | 50Hz | |
| Short-Circuit Breaking Capacity | Rated Ultimate Breaking Capacity (Icu) @ 380V | 75kA |
| Rated Service Breaking Capacity (Ics) @ 380V | 55kA | |
| Peak Withstand Current (Icw) @ 380V | 150kA | |
| Rated Breaking Capacity @ 660V | 50kA | |
| Tripping Characteristics | Tripping Type | Thermal-magnetic / Electronic (optional) |
| Instant Tripping Current | 10~14In (short circuit) | |
| Overload Tripping Time | Inverse time characteristic (1.05In no trip for 2h; 1.3In trip within 2h) | |
| Mechanical Performance | Mechanical Life | 10,000 times |
| Electrical Life | 5,000 times | |
| Structural Parameters | Pole Number | 3P / 4P |
| Protection Grade | IP30 | |
| Installation Method | Fixed type / Draw-out type | |
| Environmental Parameters | Working Temperature | -5℃ ~ +40℃ (≤95% humidity, no condensation) |
| Pollution Degree | 2 | |
| Compliance Standards | National & International Standards | GB/T 14048.2, IEC 60947-2 |